2022 Chill-Pro® Summer Claims Highlights

  • 10-year-old, 120 Ton Air cooled Screw chiller. Cause of Loss: Drive rotor fused to compressor casing

DESCRIPTION: Damage to Screw compressor while in operation. The male, or rotor driver, was found fused to the discharge wall of the compressor casing. The rotors were separated from the discharge wall during disassembly. Both the male and female rotors were found to be damaged. In addition to the damage found to the rotors, a significant amount of damage was also found on the discharge wall of the compressor. All thrust and counter thrust bearing appeared to be in good working order. The compressor required replacement as repair was not an option based on initial damage review.

  • 16-year-old, 500 Ton Centrifugal chiller. Cause of Loss: Ruptured O-Ring, refrigerant leak

DESCRIPTION: 500 Ton Centrifugal Chiller had major leaks. Loss reported as major leak on chiller. Further communication with the insured revealed that an O-Ring blew out releasing an excessive amount of freon from the system. Contractor confirmed the damage to O-Ring. It appears that O-Ring was damaged and could not hold Freon in the system. The O-Ring was replaced, and Freon was added to the system. The bulk of claim cost was refrigerant recovery.

  • 15-year-old, 80-ton Scroll chiller. Cause of Loss: Electrical arcing, failed compressor

DESCRIPTION: On date of loss, Technicians were called out when one of the six compressors on the 80-ton scroll chiller unit stopped working. Testing of the unit found that the compressor had shorted to ground. The compressor was replaced, and the unit was returned to service.

  • 10-year-old, 150 Ton Magnetic Bearing chiller. Cause of Loss: Stripped set screw, compromised seal

DESCRIPTION: Our investigation found that on the date of loss, technicians were called out to diagnose a failure on the 150 Ton magnetic bearing chiller. Technicians found the system inoperable on a temperature alarm. Initial inspection found that the system had lost most of the refrigerant in the circuit, which caused the unit to overheat and force a shut down. Technicians traced the leak to a section of the line where a screw holding the sections together had been stripped out. Due to this section no longer being sealed properly, the refrigerant was released from the system. Technicians recovered the remaining refrigerant and repaired the section of the refrigerant line. They recharged the system with R134A refrigerant and re-started the chiller.

  • 10-year-old, 450 Ton Centrifugal chiller. Cause of Loss: Circuit board failure due to power surge

DESCRIPTION: During service call chiller was found to be inoperable. Troubleshooting procedure revealed failure of 4 printed circuit boards. Replaced circuit boards and restarted 450-ton Centrifugal Chiller. No further maintenance performed.

Related posts


#

Articles

CHILL-PRO® DECEMBER 2023 NEWSLETTER

AUTUMN 2023 CLAIMS Chill-Pro® reimburses HVAC service contractors every day for their repair costs associated with unexpected breakdowns. Here’s a sample of some claims that we’ve paid contractors so far...

Continue Reading
#

Articles

2023 Chill-Pro® Autumn Claims Highlights

22-year-old Centrifugal chiller Cause of Loss: Oil Pump Failure DESCRIPTION: On date of loss, the oil pump failed on the referenced chiller causing the machine to go off on a...

Continue Reading

More in Category