  • 5-year-old Water cooled Centrifugal chiller. Cause of Loss: Compressor Arcing.
    DESCRIPTION: The stator for magnetic bearing compressor failed in the windings. Please note that the compressor was not field repairable and required entire compressor to be replaced. The compressor is traded for core and rebuilt magnetic bearing compressor installed. No other damage noted to other components associated with compressor failure.
  • 6-year-old Air cooled Screw chiller. Cause of Loss: Locked Rotor.
    DESCRIPTION: The motor that shorted to ground is related to compressor #2. Through conversations with insured, contact found metal shavings inside the compressor so we are suspecting a possible lubrication issue which may have been oil pump failure. After the new compressor was started, tech made a couple of return trips to check the oil. Minimum oil height in the oil separator is 7 inches. He measured 8 inches which means lubrication is running normal. The compressor was replaced, and unit returned to service.
  • 31-year-old Water cooled Centrifugal chiller. Cause of Loss: Compressor arcing.
    DESCRIPTION: Received an emergency service call around 5am this morning stating the chiller is tripping the main breaker. Upon arrival, technician found that the motor had shorted and seized.
    This chiller is critical to the operation of a 10-story office building. It was quicker to replace motor than attempt repair. It appears that drive line seizure may have caused damage to the motor. The motor operates 450 Tr centrifugal compressor. The labor cost to remove and reinstall motor from the roof of the building was extensive. A crane was used to remove and reinstall the motor. Refrigerant recovery service was utilized during the repair process as well. The drive was rebuilt, and new motor installed.
  • 9-year-old Air cooled Scroll chiller. Cause of Loss: Relays arcing.
    DESCRIPTION: LP & HP Transducer and sensor shorted out and required replacement.
  • 2-year-old Reciprocating chiller. Cause of Loss: Compressor arcing, grounded.
    DESCRIPTION: Technicians were called out when the compressor on chiller unit stopped functioning. Inspection of the chiller unit found that compressor Ohm tested too high. The technicians determined the compressor motor windings were open and the unit shorted to ground. The compressor has been replaced and the unit has been returned to service.

Related posts


#

Articles

CHILL-PRO® DECEMBER 2023 NEWSLETTER

AUTUMN 2023 CLAIMS Chill-Pro® reimburses HVAC service contractors every day for their repair costs associated with unexpected breakdowns. Here’s a sample of some claims that we’ve paid contractors so far...

Continue Reading
#

Articles

2023 Chill-Pro® Autumn Claims Highlights

22-year-old Centrifugal chiller Cause of Loss: Oil Pump Failure DESCRIPTION: On date of loss, the oil pump failed on the referenced chiller causing the machine to go off on a...

Continue Reading

More in Category